BFOU

P5 TriCab NFC
P5/P12 TriCab NFM
Braid Armoured VFD/VSD

0.6/1kV  90°C  >32. HCL <0.5% 
Si
m
ze
Ea
m
rth
Min. Bend
Radius mm
Nom. Cond.
OD mm
Nom. Bed.
OD mm
Nom. Braid
OD mm
Nom. Cable
OD mm
Current Rating
amp
Approx. Wt.
kg/km
3c 10 3c 4 110.2 4.0 17.3 18.3 22.05 50 814
3c 16 3c 6 118.0 5.0 18.6 19.6 23.61 67 1063
3c 25 3c 6 136.6 6.2 22.0 23.0 27.33 89 1398
3c 35 3c 6 149.6 7.4 24.4 25.4 29.92 110 1724
3c 50 3c 10 172.9 8.8 28.5 29.5 34.58 137 2392
3c 70 3c 16 196.6 10.6 32.4 33.6 39.31 169 3381
3c 95 3c 16 220.2 12.3 36.8 38.0 44.05 205 4027
3c 120 3c 25 241.6 13.9 40.6 41.8 48.32 237 5132
3c 150 3c 25 259.6 15.1 43.9 45.1 51.92 272 6016
3c 185 3c 35 287.8 16.9 49.0 50.2 57.55 311 7120
3c 240 3c 50 315.7 18.9 54.1 55.3 63.14 365 9296
3c 300 3c 50 351.2 21.5 60.4 61.6 70.23 421 11247

Conductor Comparison - TriCab versus Class 5 & 6 (approximate no.of wires)
Size mm²50 70 95 120 150 185 240 300 400 500 630
TriCab658 969 1216 1672 2052 2508 3256 4144 5368 6832 8784
Class5378 342 465 587 734 905 1174 1468 1958 1710 2155
Class6662 927 1258 1589 1987 1401 1817 2272