FH

Flexible LSZH Fire Res.
Braid VSD/VFD

0.6/1kV 125°C
Insulation X-HF-110
FH
Construction
Conductor

Fine wire plain annealed copper to IEC 60228 and AS/NZS 1125.

Flame barrier

Fire resistant, halogen free, glass mica tape.

Insulation

LSFLEX® X-125 (X-HF-110), Cross-Linked, Thermoset, Elastomeric, Low Smoke Zero Halogen.

Separator

Polypropylene tape.

Jacket

Low Friction LSFLEX® T-10 (HFS-110-TP) Flame Retardant, Low Smoke Zero Halogen, Thermoplastic. Splash resistant to oil, skydrol, petrol, acid and sea water. Resists ozone and UV. Excellent abrasion resistance. Anti-Termite/Rodent Jacket is Available.

Operating Temp
-40°C to +125°C
Voltage Rating
600/1000 Volts
Core identification
To customers specification
Jacket Colour
To customers specification
Fire Rating
WS52W
Standards
AS/NZS 1125
AS/NZS 1660.5.1
AS/NZS 1660.5.2
AS/NZS 1660.5.4
AS/NZS 1660.5.5
AS/NZS 1660.5.6
AS/NZS 3008.1
AS/NZS 3013
AS/NZS 3808
AS/NZS 5000.1
IEC 60228
IEC 60331
IEC 60332-1
IEC 60332-3-22
IEC 60754-2
IEC 60754-2
IEC 61034-1&2
Si
m
ze
Ea
m
rth
Min. Bend
Radius mm
Nom. Cond.
OD mm
Nom. Braid
OD mm
Nom. Cable
OD mm
Current Rating
amp
Approx. Wt.
kg/km

Continuous current carrying capacities are calculated assuming 40° ambient temperature in free air, flexible unenclosed touching. For other installation methods, please refer to our current ratings table.

Conductor Comparison - TriCab versus Class 5 & 6 (approximate no.of wires)
Size mm²50 70 95 120 150 185 240 300 400 500 630
TriCab658 969 1216 1672 2052 2508 3256 4144 5368 6832 8784
Class5378 342 465 587 734 905 1174 1468 1958 1710 2155
Class6662 927 1258 1589 1987 1401 1817 2272
Issue 19.0