XL

Flexible Rubber
(Fixed Wiring)

0.6/1kV 90°C
Insulation X-90
Si
m
ze
Earth
mm²
Min. Bend
Radius mm
Nom. Cond.
OD mm
Nom. Ins.
OD mm
Nom. Cable
OD mm
Current Rating
amp
Current Rating
amp
Approx. Wt.
kg/km
1c 6 22.3 3.0 4.4 7.4 51 46 92
1c 10 25.3 4.0 5.4 8.4 70 64 134
1c 16 28.3 5.0 6.4 9.4 94 85 190
1c 25 33.4 6.2 8.1 11.1 125 114 281
1c 35 36.9 7.4 9.2 12.3 155 141 373
1c 50 41.9 8.8 10.8 14.0 196 178 511
1c 70 48.1 10.6 12.8 16.0 248 225 726
1c 95 53.9 12.3 14.5 18.0 298 271 902
1c 120 61.9 14.5 17.0 20.6 354 322 1229
1c 150 69.2 16.3 19.2 23.1 409 372 1556
1c 185 75.7 18.0 21.3 25.2 470 427 1874
1c 240 83.9 20.3 23.8 28.0 565 514 2395
1c 300 91.9 22.5 26.2 30.6 650 591 3015
1c 400 105.1 26.0 30.1 35.0 780 709 3882
1c 500 116.8 29.2 33.7 38.9 903 821 4883
1c 630 129.6 32.8 37.7 43.2 1052 956 6110
2c 1.5 1.5 30.5 1.5 10.2 25 23 139
2c 2.5 2.5 34.0 2.0 11.3 33 30 187
2c 4 4 36.8 2.5 12.3 44 40 239
2c 6 6 40.4 3.0 13.5 56 51 313
2c 10 4 44.8 4.0 14.9 79 72 365
2c 16 6 51.0 5.0 17.0 106 96 513
2c 25 6 61.2 6.2 20.4 141 128 739
2c 35 10 68.4 7.4 22.8 174 158 994
2c 50 16 78.5 8.8 26.2 219 199 1360
3c 1.5 1.5 32.7 1.5 10.9 21 19 152
3c 2.5 2.5 36.7 2.0 12.2 29 26 205
3c 4 4 39.7 2.5 13.2 37 34 269
3c 6 6 43.8 3.0 14.6 47 43 358
3c 10 4 47.7 4.0 15.9 67 61 465
3c 16 6 54.5 5.0 18.2 89 81 664
3c 25 6 65.7 6.2 21.9 119 108 959
3c 35 10 73.5 7.4 24.5 149 135 1305
3c 50 16 84.4 8.8 28.1 187 170 1805
3c 70 25 99.4 10.6 33.1 235 214 2604
3c 95 25 111.5 12.3 37.2 282 256 3215
3c 120 35 128.0 14.5 42.7 333 303 4373
3c 150 50 144.5 16.3 48.2 383 348 5614
3c 185 70 159.7 18.0 53.2 436 396 6869
3c 240 95 179.0 20.3 59.7 519 472 8851
3c 300 120 200.1 22.5 66.7 593 539 11151
4c 1.5 1.5 35.4 1.5 11.8 21 19 180
4c 2.5 2.5 39.8 2.0 13.3 29 26 244
4c 4 4 43.3 2.5 14.4 37 34 323
4c 6 6 47.9 3.0 16.0 47 43 432
4c 10 4 52.5 4.0 17.5 67 61 576
4c 16 6 60.2 5.0 20.1 89 81 832
4c 25 6 72.8 6.2 24.3 119 108 1209
4c 35 10 81.6 7.4 27.2 149 135 1644
4c 50 16 94.7 8.8 31.6 187 170 2311
4c 70 25 111.4 10.6 37.1 235 214 3327
4c 95 25 125.6 12.3 41.9 282 256 4092
4c 120 35 144.4 14.5 48.1 333 303 5604
4c 150 50 162.9 16.3 54.3 383 348 7078
4c 185 70 181.0 18.0 60.3 436 396 8792

Continuous current carrying capacities are calculated assuming 40° ambient temperature in free air, flexible unenclosed touching. For other installation methods, please refer to our current ratings table.

Conductor Comparison - TriCab versus Class 5 & 6 (approximate no.of wires)
Size mm²50 70 95 120 150 185 240 300 400 500 630
TriCab658 969 1216 1672 2052 2508 3256 4144 5368 6832 8784
Class5378 342 465 587 734 905 1174 1468 1958 1710 2155
Class6662 927 1258 1589 1987 1401 1817 2272
Issue 19.0