VW

Industrial VFD
with Split Symmetric Ground

2000V 90°C
Siz
awg/
e
kcmil
Grou
awg/
nds
kcmil
Min. Bend
Radius inch
Nom. Cable
OD inch
Current Rating
amp
Approx. Wt.
lb/kft
3c 6 3g 12 6.0 1.0 75 716
3c 4 3g 12 6.7 1.1 95 923
3c 2 3g 10 7.5 1.3 130 1273
3c 1 3g 10 8.5 1.4 145 1579
3c 1/0 3g 10 9.1 1.5 170 1847
3c 2/0 3g 10 9.7 1.6 195 2183
3c 3/0 3g 8 10.4 1.7 225 2662
3c 4/0 3g 8 11.9 2.0 260 3283
3c 250 3g 6 13.0 2.2 290 3952
3c 300 3g 6 13.5 2.3 320 4507
3c 350 3g 6 14.3 2.4 350 5119
3c 400 3g 6 14.7 2.5 380 5612
3c 500 3g 6 15.9 2.6 430 6733

Continuous current carrying capacities are calculated assuming 40° ambient temperature in free air, flexible unenclosed touching. For other installation methods, please refer to our current ratings table.
There is a +5% tolerance to the NOMINAL values due to manufacturing process variations. TriCab is not liable for any errors, omissions, etc., and reserves the right to modify specifications at any time.

Issue 19.0