UX

P15 UX UPC UPM
Single conductor earthing & bonding

0.6/1kV  90°C  >32. HCL <0.5% 
Size
mm²
Min. Bend
Radius mm
Nom. Cond.
OD mm
Nom. Cable
OD mm
Current Rating
amp
Approx. Wt.
kg/km
.75 6.6 1.1 2.6 13 12
1 6.9 1.2 2.7 18 14
1.5 7.5 1.5 2.9 23 19
2.5 8.8 2.0 3.5 30 31
4 9.9 2.4 3.9 40 42
6 11.3 3.0 4.4 52 57
10 13.8 4.0 5.4 72 94
16 16.3 5.0 6.4 96 144
25 20.5 6.2 8.1 127 228
35 23.5 7.4 9.2 157 314
50 27.6 8.8 10.8 196 444
70 32.8 10.6 12.8 242 644
95 37.1 12.3 14.5 293 802
120 43.2 14.5 17.0 339 1098
150 48.8 16.3 19.2 389 1399
185 54.2 18.0 21.3 444 1701
240 60.6 20.3 23.8 522 2191
300 66.7 22.5 26.2 601 2778
400 76.7 26.0 30.1 670 3580
500 85.9 29.2 33.7 720 4529
630 96.1 32.8 37.7 780 5698

Conductor Comparison - TriCab versus Class 5 & 6 (approximate no.of wires)
Size mm²50 70 95 120 150 185 240 300 400 500 630
TriCab658 969 1216 1672 2052 2508 3256 4144 5368 6832 8784
Class5378 342 465 587 734 905 1174 1468 1958 1710 2155
Class6662 927 1258 1589 1987 1401 1817 2272
Issue 11.0