LS

Flexible LSZH Rubber
Building Wire

0.6/1kV 125°C
Insulation X-HF-110
Size
mm²
Min. Bend
Radius mm
Nom. Cond.
OD mm
Nom. Cable
OD mm
Current Rating
amp
Current Rating
amp
Approx. Wt.
kg/km
.5 5.9 0.9 2.3 13 13 9
.75 6.6 1.1 2.6 16 16 12
1 6.9 1.2 2.7 22 21 14
1.5 7.5 1.5 2.9 28 26 19
2.5 8.8 2.0 3.5 36 34 31
4 9.9 2.5 3.9 48 45 42
6 11.3 3.0 4.4 61 57 57
10 13.8 4.0 5.4 86 80 94
16 16.3 5.0 6.4 112 105 144
25 20.5 6.2 8.1 149 139 228
35 23.5 7.4 9.2 184 172 314
50 27.6 8.8 10.8 232 217 444
70 32.8 10.6 12.8 292 273 644
95 37.1 12.3 14.5 352 329 802
120 43.2 14.5 17.0 417 390 1098
150 48.8 16.3 19.2 482 450 1399
185 54.2 18.0 21.3 552 516 1701
240 60.6 20.3 23.8 663 620 2191
300 66.7 22.5 26.2 764 714 2778
400 76.7 26.0 30.1 915 855 3580
500 85.9 29.2 33.7 1059 990 4529
630 96.1 32.8 37.7 1235 1154 5698

Continuous current carrying capacities are calculated assuming 40° ambient temperature in free air, flexible unenclosed touching. For other installation methods, please refer to our current ratings table.

Conductor Comparison - TriCab versus Class 5 & 6 (approximate no.of wires)
Size mm²50 70 95 120 150 185 240 300 400 500 630
TriCab658 969 1216 1672 2052 2508 3256 4144 5368 6832 8784
Class5378 342 465 587 734 905 1174 1468 1958 1710 2155
Class6662 927 1258 1589 1987 1401 1817 2272
Issue 19.0