LP

Flexible Rubber
Building Wire

0.6/1kV 105°C
Insulation V90-HT
Size
mm²
Min. Bend
Radius mm
Nom. Cond.
OD mm
Nom. Cable
OD mm
Current Rating
amp
Current Rating
amp
Approx. Wt.
kg/km
25 40.2 7.4 10.0 100 91 116
35 45.5 8.7 11.4 122 111 150
50 55.7 10.8 13.9 150 136 208
70 62.2 12.4 15.6 191 174 276
95 72.1 14.4 18.0 238 216 376
120 79.4 16.2 19.9 278 253 458
150 87.6 17.8 21.9 320 291 565
185 99.0 20.2 24.8 373 339 709
240 108.8 22.2 27.2 448 407 909
300 124.0 25.5 31.0 519 472 1139
400 140.3 29.1 35.1 613 557 1452
500 161.5 33.9 40.4 717 652 1853
630 177.9 37.9 44.5 842 765 2326

Continuous current carrying capacities are calculated assuming 40° ambient temperature in free air, flexible unenclosed touching. For other installation methods, please refer to our current ratings table.
Issue 19.0