KDT
Flexible Nylon
Termite / Vermin Resistant SDI
0.6/1kV 110°CInsulation X-HF-110

| Size mm² |
Min. Bend Radius mm |
Nom. Cond. OD mm |
Nom. Ins. OD mm |
Nom. Cable OD mm |
Current Rating amp |
Current Rating amp |
Approx. Wt. kg/km |
|---|---|---|---|---|---|---|---|
| 6 | 63.0 | 3.0 | 4.4 | 7.9 | 61 | 57 | 94 |
| 10 | 70.9 | 4.0 | 5.4 | 8.9 | 86 | 80 | 137 |
| 16 | 79.0 | 5.0 | 6.4 | 9.9 | 112 | 105 | 192 |
| 25 | 92.5 | 6.2 | 8.1 | 11.6 | 149 | 139 | 283 |
| 35 | 101.9 | 7.4 | 9.2 | 12.7 | 184 | 172 | 375 |
| 50 | 115.1 | 8.8 | 10.8 | 14.4 | 232 | 217 | 514 |
| 70 | 133.3 | 10.6 | 12.8 | 16.7 | 292 | 273 | 736 |
| 95 | 147.1 | 12.3 | 14.5 | 18.4 | 352 | 329 | 905 |
| 120 | 168.4 | 14.5 | 17.0 | 21.1 | 417 | 390 | 1228 |
| 150 | 188.1 | 16.3 | 19.2 | 23.5 | 482 | 450 | 1554 |
| 185 | 206.9 | 18.0 | 21.3 | 25.9 | 552 | 516 | 1884 |
| 240 | 227.3 | 20.3 | 23.8 | 28.4 | 663 | 620 | 2393 |
| 300 | 248.6 | 22.5 | 26.2 | 31.1 | 764 | 714 | 3012 |
| 400 | 283.7 | 26.0 | 30.1 | 35.5 | 915 | 855 | 3877 |
| 500 | 314.8 | 29.2 | 33.7 | 39.4 | 1059 | 990 | 4877 |
| 630 | 349.1 | 32.8 | 37.7 | 43.6 | 1235 | 1154 | 6103 |
Continuous current carrying capacities are calculated assuming 40° ambient temperature in free air, flexible unenclosed touching. For other installation methods, please refer to our current ratings table.
| Conductor Comparison - TriCab versus Class 5 & 6 (approximate no.of wires) |
| Size mm² | 50 | 70 | 95 | 120 | 150 | 185 | 240 | 300 | 400 | 500 | 630 |
|---|---|---|---|---|---|---|---|---|---|---|---|
| TriCab | 658 | 969 | 1216 | 1672 | 2052 | 2508 | 3256 | 4144 | 5368 | 6832 | 8784 |
| Class5 | 378 | 342 | 465 | 587 | 734 | 905 | 1174 | 1468 | 1958 | 1710 | 2155 |
| Class6 | 662 | 927 | 1258 | 1589 | 1987 | 1401 | 1817 | 2272 |