KDT

Flexible Nylon
Termite / Vermin Resistant SDI

0.6/1kV 110°C
Insulation X-HF-110
Size
mm²
Min. Bend
Radius mm
Nom. Cond.
OD mm
Nom. Ins.
OD mm
Nom. Cable
OD mm
Current Rating
amp
Current Rating
amp
Approx. Wt.
kg/km
6 63.0 3.0 4.4 7.9 61 57 94
10 70.9 4.0 5.4 8.9 86 80 137
16 79.0 5.0 6.4 9.9 112 105 192
25 92.5 6.2 8.1 11.6 149 139 283
35 101.9 7.4 9.2 12.7 184 172 375
50 115.1 8.8 10.8 14.4 232 217 514
70 133.3 10.6 12.8 16.7 292 273 736
95 147.1 12.3 14.5 18.4 352 329 905
120 168.4 14.5 17.0 21.1 417 390 1228
150 188.1 16.3 19.2 23.5 482 450 1554
185 206.9 18.0 21.3 25.9 552 516 1884
240 227.3 20.3 23.8 28.4 663 620 2393
300 248.6 22.5 26.2 31.1 764 714 3012
400 283.7 26.0 30.1 35.5 915 855 3877
500 314.8 29.2 33.7 39.4 1059 990 4877
630 349.1 32.8 37.7 43.6 1235 1154 6103

Continuous current carrying capacities are calculated assuming 40° ambient temperature in free air, flexible unenclosed touching. For other installation methods, please refer to our current ratings table.

Conductor Comparison - TriCab versus Class 5 & 6 (approximate no.of wires)
Size mm²50 70 95 120 150 185 240 300 400 500 630
TriCab658 969 1216 1672 2052 2508 3256 4144 5368 6832 8784
Class5378 342 465 587 734 905 1174 1468 1958 1710 2155
Class6662 927 1258 1589 1987 1401 1817 2272
Issue 19.0