NB

Flexible Rubber Neutral Screened
Multi (Direct Burial)

0.6/1kV 110°C
Insulation X-HF-110
Si
m
ze
Min. Bend
Radius mm
Nom. Cond.
OD mm
Nom. Cable
OD mm
Current Rating
amp
Current Rating
amp
Approx. Wt.
kg/km
2c 6 99.1 3.0 16.5 61 64 403
2c 10 114.5 4.0 19.1 83 85 573
2c 16 130.0 5.0 21.7 154 145 803
2c 25 149.6 6.2 24.9 199 188 1130
2c 35 163.0 7.4 27.2 240 226 1468
2c 50 189.3 8.8 31.6 284 268 2046
3c 6 103.2 3.0 17.2 52 53 460
3c 10 119.4 4.0 19.9 69 71 658
3c 16 135.9 5.0 22.6 129 122 928
3c 25 157.0 6.2 26.2 167 158 1330
3c 35 171.4 7.4 28.6 201 190 1734
3c 50 198.6 8.8 33.1 240 226 2417
3c 70 224.7 10.6 37.4 294 277 3302
3c 95 246.6 12.3 41.1 353 333 4111
3c 120 283.2 14.5 47.2 402 379 5539
3c 150 311.7 16.3 51.9 452 426 6903
3c 185 338.8 18.0 56.5 510 481 8321
3c 240 379.7 20.3 63.3 591 558 10612
3c 300 410.7 22.5 68.5 667 629 13142
4c 6 117.3 3.0 19.5 52 53 623
4c 10 131.4 4.0 21.9 69 71 912
4c 16 145.6 5.0 24.3 129 122 1116
4c 25 169.3 6.2 28.2 167 158 1583
4c 35 185.5 7.4 30.9 201 190 2070
4c 50 215.2 8.8 35.9 240 226 2914
4c 70 244.3 10.6 40.7 294 277 3969
4c 95 268.9 12.3 44.8 353 333 4940
4c 120 309.1 14.5 51.5 402 379 6620
4c 150 341.0 16.3 56.8 452 426 8286
4c 185 371.4 18.0 61.9 510 481 9987

Continuous current carrying capacities are calculated assuming 40° ambient temperature in free air, flexible unenclosed touching. For other installation methods, please refer to our current ratings table.

Conductor Comparison - TriCab versus Class 5 & 6 (approximate no.of wires)
Size mm²50 70 95 120 150 185 240 300 400 500 630
TriCab658 969 1216 1672 2052 2508 3256 4144 5368 6832 8784
Class5378 342 465 587 734 905 1174 1468 1958 1710 2155
Class6662 927 1258 1589 1987 1401 1817 2272
Issue 19.0