KP
Flexible Rubber
Submersible Pump with Pilots
0.6/1kV 110°C 
m |
ze m² |
Ea m |
rth m² |
Min. Bend Radius mm |
Nom. Cond. OD mm |
Nom. Cable OD mm |
Current Rating amp |
Current Rating amp |
Approx. Wt. kg/km |
|---|---|---|---|---|---|---|---|---|---|
| 4c | 4 | 4c | 1.5 | 5.0 | 2.0 | 5.0 | 5 | 5 | 5 |
| 4c | 10 | 4c | 1.5 | 59.6 | 4.0 | 19.9 | 80 | 75 | 760 |
| 4c | 16 | 4c | 1.5 | 68.6 | 5.0 | 22.9 | 106 | 99 | 1040 |
| 4c | 25 | 4c | 1.5 | 82.9 | 6.2 | 27.6 | 140 | 131 | 1547 |
| 4c | 35 | 4c | 1.5 | 92.8 | 7.4 | 30.9 | 173 | 162 | 2047 |
| 4c | 50 | 4c | 1.5 | 106.8 | 8.8 | 35.6 | 218 | 204 | 2820 |
| 4c | 70 | 4c | 1.5 | 124.5 | 10.6 | 41.5 | 273 | 255 | 3765 |
| 4c | 95 | 4c | 1.5 | 139.8 | 12.3 | 46.6 | 327 | 306 | 4997 |
| 4c | 120 | 4c | 1.5 | 160.9 | 14.5 | 53.6 | 385 | 360 | 6184 |
| 4c | 150 | 4c | 1.5 | 180.6 | 16.3 | 60.2 | 442 | 413 | 7815 |
| 4c | 185 | 4c | 1.5 | 198.9 | 18.0 | 66.3 | 503 | 470 | 9457 |
Continuous current carrying capacities are calculated assuming 40° ambient temperature in free air, flexible unenclosed touching. For other installation methods, please refer to our current ratings table.
| Conductor Comparison - TriCab versus Class 5 & 6 (approximate no.of wires) |
| Size mm² | 50 | 70 | 95 | 120 | 150 | 185 | 240 | 300 | 400 | 500 | 630 |
|---|---|---|---|---|---|---|---|---|---|---|---|
| TriCab | 658 | 969 | 1216 | 1672 | 2052 | 2508 | 3256 | 4144 | 5368 | 6832 | 8784 |
| Class5 | 378 | 342 | 465 | 587 | 734 | 905 | 1174 | 1468 | 1958 | 1710 | 2155 |