CB
Flexible Rubber Figure 8
600V 110°CInsulation X-HF-110

m |
ze m² |
Min. Bend Radius mm |
Nom. Cond. OD mm |
Height mm |
Width mm |
Current Rating amp |
Current Rating amp |
Approx. Wt. kg/km |
|---|---|---|---|---|---|---|---|---|
| 2c | 2.5 | 19 | 1.9 | 6.3 | 13.6 | 36 | 34 | 113 |
| 2c | 4 | 21 | 2.5 | 6.8 | 14.6 | 48 | 45 | 145 |
| 2c | 6 | 22 | 3.0 | 7.4 | 15.7 | 61 | 57 | 187 |
| 2c | 10 | 25 | 4.0 | 8.5 | 17.7 | 86 | 80 | 273 |
| 2c | 16 | 28 | 5.0 | 9.5 | 19.8 | 112 | 105 | 385 |
| 2c | 25 | 33 | 6.2 | 11.1 | 23.3 | 149 | 139 | 567 |
| 2c | 35 | 37 | 7.4 | 12.3 | 25.7 | 184 | 172 | 752 |
| 2c | 50 | 42 | 8.8 | 14.0 | 29.2 | 233 | 218 | 1029 |
Continuous current carrying capacities are calculated assuming 40° ambient temperature in free air, flexible unenclosed touching. For other installation methods, please refer to our current ratings table.
Issue 19.0