BIOI BICI Offshore Braid Armour Fire Res.
Power & Control

0.6/1kV  110°C  >32. HCL <0.5% 
Si
m
ze
Min. Bend
Radius mm
Nom. Cond.
OD mm
Nom. Bed.
OD mm
Nom. Braid
OD mm
Nom. Cable
OD mm
Current Rating
amp
Approx. Wt.
kg/km
2c 1.5 65 1.5 9.4 10.2 13.0 20 199
2c 2.5 72 1.9 10.6 11.4 14.4 26 249
2c 4 77 2.5 11.7 12.5 15.4 34 297
2c 6 83 3.0 12.8 13.6 16.5 44 357
2c 10 95 4.0 14.9 15.7 19.0 61 493
2c 16 107 5.0 17.0 17.8 21.3 82 659
2c 25 125 6.2 20.4 21.2 25.0 108 932
2c 35 137 7.4 22.6 23.4 27.4 133 1184
3c 1.5 67 1.5 10.0 10.8 13.5 16 222
3c 2.5 75 1.9 11.3 12.1 15.0 21 283
3c 4 81 2.5 12.3 13.1 16.1 28 345
3c 6 89 3.0 13.8 14.6 17.7 36 437
3c 10 100 4.0 15.8 16.6 20.1 50 605
3c 16 113 5.0 18.1 18.9 22.6 67 823
3c 25 133 6.2 21.7 22.5 26.5 89 1179
3c 35 147 7.4 24.3 25.1 29.4 110 1527
3c 50 166 8.8 27.8 28.6 33.2 137 2043
3c 70 191 10.6 32.3 33.1 38.1 169 2844
3c 95 212 12.3 36.1 36.9 42.4 205 3504
3c 120 235 13.9 40.3 41.1 46.9 237 4378
3c 150 254 15.1 43.8 44.6 50.9 272 5335
3c 185 282 16.9 48.7 49.5 56.3 311 6197
3c 240 310 18.9 53.8 54.6 61.9 365 8035
4c 1.5 74 1.5 11.1 11.9 14.8 16 267
4c 2.5 80 1.9 12.3 13.1 16.0 21 327
4c 4 89 2.5 13.7 14.5 17.7 28 418
4c 6 95 3.0 15.0 15.8 19.1 36 517
4c 10 109 4.0 17.5 18.3 21.8 50 735
4c 16 122 5.0 19.9 20.7 24.4 67 1002
4c 25 146 6.2 24.1 24.9 29.2 89 1470
4c 35 161 7.4 27.0 27.8 32.2 110 1914
4c 50 184 8.8 30.9 31.7 36.7 137 2588
4c 70 211 10.6 35.9 36.7 42.2 169 3612
4c 95 235 12.3 40.3 41.1 46.9 205 4444
4c 120 260 13.9 44.8 45.6 51.9 237 5568
4c 150 282 15.1 48.7 49.5 56.3 272 6793
4c 185 313 16.9 54.4 55.2 62.5 311 7894
5c 1.5 80 1.5 12.2 13.0 15.9 16 304
5c 2.5 89 1.9 13.7 14.5 17.7 21 391
5c 4 95 2.5 15.1 15.9 19.1 28 486
5c 6 105 3.0 16.6 17.4 20.9 36 614
5c 10 119 4.0 19.4 20.2 23.9 50 879
5c 16 135 5.0 22.2 23.0 27.0 67 1214
5c 25 161 6.2 27.0 27.8 32.2 89 1784
5c 35 177 7.4 30.0 30.8 35.5 110 2315
5c 50 203 8.8 34.6 35.4 40.7 137 3154
5c 70 235 10.6 40.4 41.2 46.9 169 4425
5c 95 261 12.3 45.1 45.9 52.2 205 5450
5c 120 290 13.9 50.3 51.1 57.9 237 6847
5c 150 314 15.1 54.7 55.5 62.8 272 8357
5c 185 349 16.9 61.0 61.8 69.9 311 9727
7c 1.5 86 1.5 13.3 14.1 17.2 12 354
7c 2.5 95 1.9 15.4 16.2 19.0 16 452
10c 1.5 107 1.5 17.1 17.9 21.3 11 493
10c 2.5 118 1.9 19.7 20.5 23.6 14 632
12c 1.5 111 1.5 17.8 18.6 22.1 10 546
12c 2.5 122 1.9 20.7 21.5 24.4 13 708
14c 1.5 116 1.5 18.7 19.5 23.3 10 612
14c 2.5 129 1.9 21.8 22.6 25.8 12 806
16c 1.5 121 1.5 19.8 20.6 24.3 9 672
16c 2.5 136 1.9 23.1 23.9 27.1 12 889
19c 1.5 129 1.5 21.1 21.9 25.8 9 772
19c 2.5 144 1.9 24.6 25.4 28.8 11 1025
24c 1.5 149 1.5 24.7 25.5 29.8 8 959
24c 2.5 166 1.9 28.8 29.6 33.2 10 1274
27c 1.5 152 1.5 25.5 26.3 30.5 8 1034
27c 2.5 171 1.9 29.7 30.5 34.2 10 1397
33c 1.5 165 1.5 27.6 28.4 32.9 7 1221
33c 2.5 185 1.9 32.2 33.0 36.9 9 1654
37c 1.5 171 1.5 28.7 29.5 34.2 7 1340
37c 2.5 191 1.9 33.7 34.5 38.1 9 1802

IEC 60092-352:2005 Table B.4 - Current carrying capacities in continuous service, 90°C operating temperature, 45°C ambient air temperature.

Conductor Comparison - TriCab versus Class 5 & 6 (approximate no.of wires)
Size mm²50 70 95 120 150 185 240 300 400 500 630
TriCab658 969 1216 1672 2052 2508 3256 4144 5368 6832 8784
Class5378 342 465 587 734 905 1174 1468 1958 1710 2155
Class6662 927 1258 1589 1987 1401 1817 2272