XDT
Flexible Nylon
Vermin Resistant SDI
0.6/1kV 90°CInsulation X-90

| Size awg/kcmil |
Min. Bend Radius inch |
Nom. Cond. OD inch |
Nom. Ins. OD inch |
Nom. Cable OD inch |
Current Rating amp |
Current Rating amp |
Approx. Wt. lb/kft |
|---|---|---|---|---|---|---|---|
| 6 | 63 | 3.0 | 4.4 | 7.9 | 51 | 46 | 94 |
| 10 | 71 | 4.0 | 5.4 | 8.9 | 70 | 64 | 137 |
| 16 | 79 | 5.0 | 6.4 | 9.9 | 94 | 85 | 193 |
| 25 | 92 | 6.2 | 8.1 | 11.5 | 125 | 114 | 284 |
| 35 | 102 | 7.4 | 9.2 | 12.8 | 155 | 141 | 375 |
| 50 | 115 | 8.8 | 10.8 | 14.4 | 196 | 178 | 514 |
| 70 | 133 | 10.6 | 12.9 | 16.6 | 248 | 225 | 735 |
| 95 | 147 | 12.3 | 14.5 | 18.4 | 298 | 271 | 905 |
| 120 | 163 | 13.9 | 16.4 | 20.4 | 354 | 322 | 1148 |
| 150 | 176 | 15.1 | 17.9 | 22.0 | 409 | 372 | 1409 |
| 185 | 197 | 16.9 | 20.2 | 24.6 | 470 | 427 | 1627 |
| 240 | 216 | 18.9 | 22.4 | 27.0 | 565 | 514 | 2156 |
| 300 | 241 | 21.5 | 25.2 | 30.1 | 650 | 591 | 2724 |
| 400 | 270 | 24.5 | 28.6 | 33.8 | 780 | 709 | 3360 |
| 500 | 298 | 27.3 | 31.8 | 37.2 | 903 | 821 | 4014 |
| 630 | 326 | 30.2 | 35.1 | 40.8 | 1052 | 956 | 5071 |
Continuous current carrying capacities are calculated assuming 40° ambient temperature in free air, flexible unenclosed touching. For other installation methods, please refer to our current ratings table.
| Conductor Comparison - TriCab versus Class 5 & 6 (approximate no.of wires) |
| Size mm² | 50 | 70 | 95 | 120 | 150 | 185 | 240 | 300 | 400 | 500 | 630 |
|---|---|---|---|---|---|---|---|---|---|---|---|
| TriCab | 658 | 969 | 1216 | 1672 | 2052 | 2508 | 3256 | 4144 | 5368 | 6832 | 8784 |
| Class5 | 378 | 342 | 465 | 587 | 734 | 905 | 1174 | 1468 | 1958 | 1710 | 2155 |
| Class6 | 662 | 927 | 1258 | 1589 | 1987 | 1401 | 1817 | 2272 |