1.9/3.3kV 110°C

Unscreened SDI single power

Medium Voltage

V1
Construction
Conductor

Fine wire tinned annealed copper to IEC 60228 and AS/NZS 1125.

Insulation

LSFLEX® E-125 (R-EP-125) High Grade EPR insulation type 3GI3 to VDE 0207 part 20, Crosslinked, Thermoset, Elastomeric, Low Smoke Zero Halogen. 125°C max operating temperature conforms to UL1581.

Jacket

Low-Friction E-RUBBER® S-20 Thermoplastic, Elastomeric, Flame Retardant. Splash resistant to oil, skydrol, petrol, acid and sea water. Resists ozone and UV. Excellent abrasion resistance. Submersible to 500m. Best Practice PVC. Anti-Termite/Rodent Jacket is Available.

Operating Temp
-15°C to +110°C
Voltage Rating
1900/3300 Volts
Core Colour
White
Jacket Colour
Black or to customer specification
Standards
VDE 0207/20
VDE 0250/602
UL 1581
AS/NZS 1125
AS/NZS 3008.1
AS/NZS 1660.5.1
AS/NZS 1660.5.6
IEC 60228
IEC 60332-1
Compliance
GreenStar Compliance
Si
m
ze
Min. Bend
Radius mm
Nom. Cond.
OD mm
Nom. Ins.
OD mm
Nom. Cable
OD mm
Current Rating
amp
Approx. Wt.
kg/km

Continuous current carrying capacities are calculated assuming 40° ambient temperature in free air, flexible unenclosed touching. For other installation methods, please refer to our current ratings table.

Conductor Comparison - TriCab versus Class 5 & 6 (approximate no.of wires)
Size mm²50 70 95 120 150 185 240 300 400 500 630
TriCab658 969 1216 1672 2052 2508 3256 4144 5368 6832 8784
Class5378 342 465 587 734 905 1174 1468 1958 1710 2155
Class6662 927 1258 1589 1987 1401 1817 2272
Issue 19.0